Medium-voltage Inverter

WIN-HV Series medium-voltage frequency inverter


Power range

Voltage3kV10kV  Single-unit power315kW12000kW

Product’s introduction

The WINNER WIN-HV series medium-voltage frequency inverter designed and manufactured by WINNER has prominent performance and high reliability with low cost. It is of AC-DC-AC voltage type inverter with main loop of multi-level topology circuit. The control mode adopts SPWM technology. And the input uses isolated transformer of multiple technology, while the output is fulfilled by the solution of phase-shifting tandem multi-unit and medium-voltage to medium-voltage direct conversion.

Many years of technical experience enabled Winner and its staff to have developed inverters with low harmonic content, which is in a leading level in domestic. Perfect output voltage sine wave provides the inverter with stability of motor’s operation during the whole speed regulation range. The low input current harmonics almost has no any disturbance to the grid and this ensures the operation reliability of the surrounding electric equipments.

This series inverter can drive and regulate the medium-voltage motor in almost all kinds of application area. The speed regulation is smooth, and the efficiency and power factor is enviable.  In particular, nowadays the world is in short of energy. Winner inverter can bring great economic effect when used for blowers and pumps.

This series inverter consists of three main parts, transformer cabinet is on the left, and power unit cabinet is in the middle, while control cabinet is on the right. To improve the stability of the control circuit and to make the debugging more convenient, the control cabinet door was put on the right of the machine.  This series product adopts cabinet structure with forced air cooling. And the big capacity machine adopts the cooling mode of water-cooled, air-closed circulation.   The wiring terminal of input and output of the complete machine was placed on the lower left back. It is easy for connection

Application area

WIN-HV medium-voltage frequency inverter has been widely used for the medium-voltage motor’s speed regulation, energy saving, soft starting and intelligent control in the area of power supply, iron and steel, HVAC, oil, construction, mine and etc.

  • Heat power station: coal grinding machine, blower, draught fan, dust exhaust fan, circulating pump, water-feeding pump.
  • Iron and steel plant, metallurgical plant: water-feeding pump, dust exhaust fan, draught fan, oxygenator.
  • Mine: slurry pump, ventilator.
  • Oil: water injection pump, oil pump.
  • Chemical plant: compressor, blower, circulating pump.
  • draw off pump, supply pump, purifying pump, sewage pump in urban power supply and sewage disposal:
  • The grinder, pump, draught fan, dust fan, supply blower in cement plant and ceramic plant
  • others: the blower for medicine, paper making, food

Feature

Years of accumulative technology of high-power drive increases the product’s power supply to be 8000kw.
Unique low-induction bus structure ensures stable operation of the power unit.
Distinctive cooling design and components layout enable the inverter to work more reliably.

Non-disturbance switch between grid frequency and inverted frequency makes sure that the equipments can work uninterruptedly.

Standard Wiring Diagram

Classification

Parameters

Range

Unit

Increment

Factory Default

Drive parameters

Reference frequency

40.050.0

Hz

0.1Hz

50

Reference voltage

150010000

V

1V

variable

Maximum frequency

060

Hz

0.1Hz

50

upper limit frequency

060

Hz

0.1Hz

51

lower limit frequency

060

Hz

0.1Hz

3.0

Starting frequency

05

Hz

0.1Hz

0.5

acceleration time

1255

4s

1

15

deceleration time

1255

4s

1

15

torque boost

015

1

1

1

Overload multiple

10150

%

1

150

unit bypass level

02

 

1

1

frequency inverter address

031

1

 

2

Function parameters

host input selection

With, without

 

 

without

host control selection

withwithout

 

 

without

control status

open loop or closed loop

 

 

open loop

operating mode

Local or remote

 

 

local

input mode

digitalanalogmulti-step speed

 

 

digital

analog input option

05V/020mA

V/mA

 

05V

Analog output option3 ways

 

 

 

As per manual

Bypass option

withwithout

 

 

without

 parameters

Motor rated power

08000

kW

1kW

As per specification

motor rated current

0600

A

0.1A

As per specification

Motor over load multiple

120150

%

1

150

Number of motor poles

210

\

1

4

Motor rated speed

1803600

Rpm

1

1480

status parameters

Input frequency

050

Hz

0.1Hz

 

operation speed

 

Rpm

 

 

Operating frequency

051

Hz

0.1Hz

 

output current

 

A

0.1A

 

Output voltage

 

V

 

 

Output power

 

kW

 

 

Continuous operating time

 

h

0.1h

 


Specification

Item

Specification

power input

Input frequency

50/60Hz±3%

Input voltage

T30:3kVT60: 6kV,  T100: 10kV(-20% +15%)

Allowed time of power fail

100ms

Input power factor

In the event of rated load > 0.97

efficiency

In the event of rated load > 96 %( inverter part> 98%)

control characteristics

control mode

SPWM; tandem unit; phase-shift superposed wave; ac-dc-ac; medium-voltage to medium-voltage; technology

Output frequency

0 60Hz

Output frequency precision

0.1Hz

Overload capacity

120%1minute150% 2s160% immediate protection(heavy load type:150%1minute180% 2s200% immediate protection)

acceleration and deceleration time

6 1200s

Analog input

05V020mA, 420mA(2 ports)

Analog output

010V,020mA,420mA voltagecurrentfrequency optional(3 ways)

Analog feedback

05V420mA(2 ports)

Host communication

RS-485interface isolation

Switching value, input/output

24ways/16ways

protecting functions

Over currentoverloadshortcutthree phase current unbalanceinstantaneous power failureinputoutput phase faultover voltageunder voltagebody overheattransformer overheatexterior fault outagepower unit auto bypass

environment

Operating environment temperature

0 +40

Storage temperature

-40 +70

Cooling mode

Forced air cooling

Environment humidity

< 90%no condensation

Altitude

< 1000 meters

Protection level

IP30


 

Item

Content

WIN-HV_ T30

077

096

120

154

192

240

290

Inverter capacity (kVA)

400

500

630

800

1000

1250

1600

output of adaptive motor(kW)

315

400

500

630

800

1000

1250

rated output current(A)

77

96

120

154

192

240

308

Number of tandem unit of each phase

5

Exterior dimension(W×H×D)

3700×2350×1100

4200×2450×1200

6400×2750×1300

weight(kg)

3500 4200

4500 6000

6000 8500

 

Item

Content

WIN-HV_T60

039

048

061

077

096

120

154

173

192

220

240

304

384

480

540

600

Inverter capacity (kVA)

400

500

630

800

1000

1250

1600

1800

2000

2250

2500

3150

4000

5000

5600

6250

output of adaptive motor(kW)

315

400

500

630

800

1000

1250

1400

1600

1800

2000

2500

3150

4000

4500

5000

rated output current(A)

39

48

61

77

96

120

154

173

192

220

240

304

384

480

540

600

Number of tandem unit of each phase

6

Exterior dimension(W×H×D)

3350×2350×1100

3700×2350×1100

4200×2450×1200

6400×2750×1300

6500×3300×2100

weight(kg)

25002800

30503850

44004850

65009050

1230014400

 

Item

Content

WIN-HV_T100

023

029

036

046

058

072

092

104

115

130

144

182

230

290

323

360

433

580

Inverter capacity(kVA)

400

500

630

800

1000

1250

1600

1800

2000

2250

2500

3150

4000

5000

5600

6250

7500

10000

output of adaptive motor(kW)

315

400

500

630

800

1000

1250

1400

1600

1800

2000

2500

3150

4000

4500

5000

6000

8000

rated output current(A)

23

29

36

46

58

72

92

104

115

130

144

182

230

290

323

360

433

580

Number of tandem unit of each phase

9

Exterior dimension(W×H×D)

4300×2350×1100

4750×2350×1200

5600×2750×1200

8500×2750×1300

8200×3300×2100

weight(kg)

30003800

42505300

61007950

1020012800

1600022300