Medium-voltage Inverter
WIN-HV Series medium-voltage frequency inverter
Power range
Voltage:3kV~10kV Single-unit power:315kW~12000kW
Product’s introduction
The WINNER WIN-HV series medium-voltage frequency inverter designed and manufactured by WINNER has prominent performance and high reliability with low cost. It is of AC-DC-AC voltage type inverter with main loop of multi-level topology circuit. The control mode adopts SPWM technology. And the input uses isolated transformer of multiple technology, while the output is fulfilled by the solution of phase-shifting tandem multi-unit and medium-voltage to medium-voltage direct conversion.
Many years of technical experience enabled Winner and its staff to have developed inverters with low harmonic content, which is in a leading level in domestic. Perfect output voltage sine wave provides the inverter with stability of motor’s operation during the whole speed regulation range. The low input current harmonics almost has no any disturbance to the grid and this ensures the operation reliability of the surrounding electric equipments.
This series inverter can drive and regulate the medium-voltage motor in almost all kinds of application area. The speed regulation is smooth, and the efficiency and power factor is enviable. In particular, nowadays the world is in short of energy. Winner inverter can bring great economic effect when used for blowers and pumps.
This series inverter consists of three main parts, transformer cabinet is on the left, and power unit cabinet is in the middle, while control cabinet is on the right. To improve the stability of the control circuit and to make the debugging more convenient, the control cabinet door was put on the right of the machine. This series product adopts cabinet structure with forced air cooling. And the big capacity machine adopts the cooling mode of water-cooled, air-closed circulation. The wiring terminal of input and output of the complete machine was placed on the lower left back. It is easy for connection
Application area
WIN-HV medium-voltage frequency inverter has been widely used for the medium-voltage motor’s speed regulation, energy saving, soft starting and intelligent control in the area of power supply, iron and steel, HVAC, oil, construction, mine and etc.
- Heat power station: coal grinding machine, blower, draught fan, dust exhaust fan, circulating pump, water-feeding pump.
- Iron and steel plant, metallurgical plant: water-feeding pump, dust exhaust fan, draught fan, oxygenator.
- Mine: slurry pump, ventilator.
- Oil: water injection pump, oil pump.
- Chemical plant: compressor, blower, circulating pump.
- draw off pump, supply pump, purifying pump, sewage pump in urban power supply and sewage disposal:
- The grinder, pump, draught fan, dust fan, supply blower in cement plant and ceramic plant
- others: the blower for medicine, paper making, food
Feature
Years of accumulative technology of high-power drive increases the product’s power supply to be 8000kw.
Unique low-induction bus structure ensures stable operation of the power unit.
Distinctive cooling design and components layout enable the inverter to work more reliably.
Non-disturbance switch between grid frequency and inverted frequency makes sure that the equipments can work uninterruptedly.
Standard Wiring Diagram |
|||||
Classification |
Parameters |
Range |
Unit |
Increment |
Factory Default |
Drive parameters |
Reference frequency |
40.0~50.0 |
Hz |
0.1Hz |
50 |
Reference voltage |
1500~10000 |
V |
1V |
variable |
|
Maximum frequency |
0~60 |
Hz |
0.1Hz |
50 |
|
upper limit frequency |
0~60 |
Hz |
0.1Hz |
51 |
|
lower limit frequency |
0~60 |
Hz |
0.1Hz |
3.0 |
|
Starting frequency |
0~5 |
Hz |
0.1Hz |
0.5 |
|
acceleration time |
1~255 |
4s |
1 |
15 |
|
deceleration time |
1~255 |
4s |
1 |
15 |
|
torque boost |
0~15 |
1 |
1 |
1 |
|
Overload multiple |
10~150 |
% |
1 |
150 |
|
unit bypass level |
0~2 |
|
1 |
1 |
|
frequency inverter address |
0~31 |
1 |
|
2 |
|
Function parameters |
host input selection |
With, without |
|
|
without |
host control selection |
with、without |
|
|
without |
|
control status |
open loop or closed loop |
|
|
open loop |
|
operating mode |
Local or remote |
|
|
local |
|
input mode |
digital、analog、multi-step speed |
|
|
digital |
|
analog input option |
0~5V/0~20mA |
V/mA |
|
0~5V |
|
Analog output option(3 ways) |
|
|
|
As per manual |
|
Bypass option |
with、without |
|
|
without |
|
parameters |
Motor rated power |
0~8000 |
kW |
1kW |
As per specification |
motor rated current |
0~600 |
A |
0.1A |
As per specification |
|
Motor over load multiple |
120~150 |
% |
1 |
150 |
|
Number of motor poles |
2~10 |
\ |
1 |
4 |
|
Motor rated speed |
180~3600 |
Rpm |
1 |
1480 |
|
status parameters |
Input frequency |
0~50 |
Hz |
0.1Hz |
|
operation speed |
|
Rpm |
|
|
|
Operating frequency |
0~51 |
Hz |
0.1Hz |
|
|
output current |
|
A |
0.1A |
|
|
Output voltage |
|
V |
|
|
|
Output power |
|
kW |
|
|
|
Continuous operating time |
|
h |
0.1h |
|
Specification |
||
Item |
Specification |
|
power input |
Input frequency |
50/60Hz±3% |
Input voltage |
T30:3kV,T60: 6kV, T100: 10kV(-20% ~ +15%) |
|
Allowed time of power fail |
100ms |
|
Input power factor |
In the event of rated load > 0.97 |
|
efficiency |
In the event of rated load > 96 %( inverter part> 98%) |
|
control characteristics |
control mode |
SPWM; tandem unit; phase-shift superposed wave; ac-dc-ac; medium-voltage to medium-voltage; technology |
Output frequency |
0 ~ 60Hz |
|
Output frequency precision |
0.1Hz |
|
Overload capacity |
120%1minute,150% 2s,160% immediate protection(heavy load type:150%1minute,180% 2s,200% immediate protection) |
|
acceleration and deceleration time |
6 ~ 1200s |
|
Analog input |
0~5V,0~20mA, 4~20mA(2 ports) |
|
Analog output |
0~10V,0~20mA,4~20mA voltage、current、frequency optional(3 ways) |
|
Analog feedback |
0~5V,4~20mA(2 ports) |
|
Host communication |
RS-485interface isolation |
|
Switching value, input/output |
24ways/16ways |
|
protecting functions |
Over current,overload,shortcut,three phase current unbalance,instantaneous power failure,input、output phase fault,over voltage,under voltage,body overheat,transformer overheat,exterior fault outage,power unit auto bypass |
|
environment |
Operating environment temperature |
0℃ ~ +40℃ |
Storage temperature |
-40℃ ~ +70℃ |
|
Cooling mode |
Forced air cooling |
|
Environment humidity |
< 90%(no condensation) |
|
Altitude |
< 1000 meters |
|
Protection level |
IP30 |
Item |
Content |
||||||
WIN-HV_ T30 |
077 |
096 |
120 |
154 |
192 |
240 |
290 |
Inverter capacity (kVA) |
400 |
500 |
630 |
800 |
1000 |
1250 |
1600 |
output of adaptive motor(kW) |
315 |
400 |
500 |
630 |
800 |
1000 |
1250 |
rated output current(A) |
77 |
96 |
120 |
154 |
192 |
240 |
308 |
Number of tandem unit of each phase |
5 |
||||||
Exterior dimension(W×H×D) |
3700×2350×1100 |
4200×2450×1200 |
6400×2750×1300 |
||||
weight(kg) |
3500 ~ 4200 |
4500 ~ 6000 |
6000 ~ 8500 |
Item |
Content |
|||||||||||||||
WIN-HV_T60 |
039 |
048 |
061 |
077 |
096 |
120 |
154 |
173 |
192 |
220 |
240 |
304 |
384 |
480 |
540 |
600 |
Inverter capacity (kVA) |
400 |
500 |
630 |
800 |
1000 |
1250 |
1600 |
1800 |
2000 |
2250 |
2500 |
3150 |
4000 |
5000 |
5600 |
6250 |
output of adaptive motor(kW) |
315 |
400 |
500 |
630 |
800 |
1000 |
1250 |
1400 |
1600 |
1800 |
2000 |
2500 |
3150 |
4000 |
4500 |
5000 |
rated output current(A) |
39 |
48 |
61 |
77 |
96 |
120 |
154 |
173 |
192 |
220 |
240 |
304 |
384 |
480 |
540 |
600 |
Number of tandem unit of each phase |
6 |
|||||||||||||||
Exterior dimension(W×H×D) |
3350×2350×1100 |
3700×2350×1100 |
4200×2450×1200 |
6400×2750×1300 |
6500×3300×2100 |
|||||||||||
weight(kg) |
2500~2800 |
3050~3850 |
4400~4850 |
6500~9050 |
12300~14400 |
Item |
Content |
||||||||||||||||||
WIN-HV_T100 |
023 |
029 |
036 |
046 |
058 |
072 |
092 |
104 |
115 |
130 |
144 |
182 |
230 |
290 |
323 |
360 |
433 |
580 |
|
Inverter capacity(kVA) |
400 |
500 |
630 |
800 |
1000 |
1250 |
1600 |
1800 |
2000 |
2250 |
2500 |
3150 |
4000 |
5000 |
5600 |
6250 |
7500 |
10000 |
|
output of adaptive motor(kW) |
315 |
400 |
500 |
630 |
800 |
1000 |
1250 |
1400 |
1600 |
1800 |
2000 |
2500 |
3150 |
4000 |
4500 |
5000 |
6000 |
8000 |
|
rated output current(A) |
23 |
29 |
36 |
46 |
58 |
72 |
92 |
104 |
115 |
130 |
144 |
182 |
230 |
290 |
323 |
360 |
433 |
580 |
|
Number of tandem unit of each phase |
9 |
||||||||||||||||||
Exterior dimension(W×H×D) |
4300×2350×1100 |
4750×2350×1200 |
5600×2750×1200 |
8500×2750×1300 |
8200×3300×2100 |
||||||||||||||
weight(kg) |
3000~3800 |
4250~5300 |
6100~7950 |
10200~12800 |
16000~22300 |
||||||||||||||